Understanding power transformer frequency response analysis signatures

This paper presents a comprehensive analysis of the effects of various faults on the FRA signatures of a transformer simulated by a high-frequency model. The faults were simulated through changes in the values of some of the electrical components in the model. It was found that radial displacement o...

Full description

Bibliographic Details
Main Authors: Abu Siada, Ahmed, Hashemnia, Naser, Islam, Syed, Masoum, Mohammad
Format: Journal Article
Published: IEEE Dielectrics and Electrical Insulation Society 2013
Online Access:http://hdl.handle.net/20.500.11937/24178