Lightning Protection Of Pole-Mounted Transformers And Its Applications
Lightning is the single most important cause of failure in medium voltage distribution system. Analysis carried out by world wide utilities has shown that the failure rate of the pole-mounted transformer caused by lightning in medium voltage system goes as high as 4.5-5.0%. This is mainly due...
| Main Author: | |
|---|---|
| Format: | Monograph |
| Language: | English |
| Published: |
Universiti Sains Malaysia
2006
|
| Subjects: | |
| Online Access: | http://eprints.usm.my/58733/ http://eprints.usm.my/58733/1/Lightning%20Protection%20Of%20Pole-Mounted%20Transformers%20And%20Its%20Applications_Chan%20Chee%20Pin.pdf |
| _version_ | 1848883978613817344 |
|---|---|
| author | Chan, Chee Pin |
| author_facet | Chan, Chee Pin |
| author_sort | Chan, Chee Pin |
| building | USM Institutional Repository |
| collection | Online Access |
| description | Lightning is the single most important cause of failure in medium voltage
distribution system. Analysis carried out by world wide utilities has shown that the failure
rate of the pole-mounted transformer caused by lightning in medium voltage system goes
as high as 4.5-5.0%. This is mainly due to improper installation of lightning arrester and
also there is no well established method to access the performance of lightning protection.
The objectives of this study are to provide a general bench mark for lightning protection of
pole-mounted transformer in medium voltage system and to ensure proper installation of
surge arrester to reduce the failure rate of the transformer. Research has found out that the
high failure rate of pole-mounted transformer is due to the excessive separation length
between the surge arrester and the terminal of the transformer. A method has been
proposed that the separation length is determined so that the failure rate of the transformer
is below a certain value. With this method, a case study on the lightning protection of pole-mounted transformer of 11kV distribution system in Malaysia is carried out. A program
prototype based on this method is also developed with Matlab to deal with the tedious hand
calculations of integration and probability. This program is applied to the case study above
to further verify the results of hand calculation. In this case study, with parameters of
ground flash density (Ng) = 5.8 flashes per m2 per year, horizontal span of two outmost
conductors (b) = 1.07m, conductor height (H) = 7.525m, shielding factor (Sf) = 0.4,
transformer lifetime (LF) = 20 years, failure rate (FR) = 5%, maximum surge current (I0) =
300kA, safety margin (sm) = 20%, residual voltage of arrester (Up) = 32kV, basic
insulation level (BIL) = 75kV, wave front time (tf) = 5µs, line surge impedance (Z0) =
450Ω, and arrester length (lmin) = 1m, the optimum separation length calculated by the
program is 1.3219m. This means that in order to achieve a failure rate of 5% throughout
the lifetime of the transformer, surge arrester should be installed 1.3219m from the
transformer terminal. |
| first_indexed | 2025-11-15T18:59:24Z |
| format | Monograph |
| id | usm-58733 |
| institution | Universiti Sains Malaysia |
| institution_category | Local University |
| language | English |
| last_indexed | 2025-11-15T18:59:24Z |
| publishDate | 2006 |
| publisher | Universiti Sains Malaysia |
| recordtype | eprints |
| repository_type | Digital Repository |
| spelling | usm-587332023-05-30T08:05:33Z http://eprints.usm.my/58733/ Lightning Protection Of Pole-Mounted Transformers And Its Applications Chan, Chee Pin T Technology TK Electrical Engineering. Electronics. Nuclear Engineering Lightning is the single most important cause of failure in medium voltage distribution system. Analysis carried out by world wide utilities has shown that the failure rate of the pole-mounted transformer caused by lightning in medium voltage system goes as high as 4.5-5.0%. This is mainly due to improper installation of lightning arrester and also there is no well established method to access the performance of lightning protection. The objectives of this study are to provide a general bench mark for lightning protection of pole-mounted transformer in medium voltage system and to ensure proper installation of surge arrester to reduce the failure rate of the transformer. Research has found out that the high failure rate of pole-mounted transformer is due to the excessive separation length between the surge arrester and the terminal of the transformer. A method has been proposed that the separation length is determined so that the failure rate of the transformer is below a certain value. With this method, a case study on the lightning protection of pole-mounted transformer of 11kV distribution system in Malaysia is carried out. A program prototype based on this method is also developed with Matlab to deal with the tedious hand calculations of integration and probability. This program is applied to the case study above to further verify the results of hand calculation. In this case study, with parameters of ground flash density (Ng) = 5.8 flashes per m2 per year, horizontal span of two outmost conductors (b) = 1.07m, conductor height (H) = 7.525m, shielding factor (Sf) = 0.4, transformer lifetime (LF) = 20 years, failure rate (FR) = 5%, maximum surge current (I0) = 300kA, safety margin (sm) = 20%, residual voltage of arrester (Up) = 32kV, basic insulation level (BIL) = 75kV, wave front time (tf) = 5µs, line surge impedance (Z0) = 450Ω, and arrester length (lmin) = 1m, the optimum separation length calculated by the program is 1.3219m. This means that in order to achieve a failure rate of 5% throughout the lifetime of the transformer, surge arrester should be installed 1.3219m from the transformer terminal. Universiti Sains Malaysia 2006-05-01 Monograph NonPeerReviewed application/pdf en http://eprints.usm.my/58733/1/Lightning%20Protection%20Of%20Pole-Mounted%20Transformers%20And%20Its%20Applications_Chan%20Chee%20Pin.pdf Chan, Chee Pin (2006) Lightning Protection Of Pole-Mounted Transformers And Its Applications. Project Report. Universiti Sains Malaysia, Pusat Pengajian Kejuruteraan Elektrik dan Elektronik. (Submitted) |
| spellingShingle | T Technology TK Electrical Engineering. Electronics. Nuclear Engineering Chan, Chee Pin Lightning Protection Of Pole-Mounted Transformers And Its Applications |
| title | Lightning Protection Of Pole-Mounted Transformers And Its Applications |
| title_full | Lightning Protection Of Pole-Mounted Transformers And Its Applications |
| title_fullStr | Lightning Protection Of Pole-Mounted Transformers And Its Applications |
| title_full_unstemmed | Lightning Protection Of Pole-Mounted Transformers And Its Applications |
| title_short | Lightning Protection Of Pole-Mounted Transformers And Its Applications |
| title_sort | lightning protection of pole-mounted transformers and its applications |
| topic | T Technology TK Electrical Engineering. Electronics. Nuclear Engineering |
| url | http://eprints.usm.my/58733/ http://eprints.usm.my/58733/1/Lightning%20Protection%20Of%20Pole-Mounted%20Transformers%20And%20Its%20Applications_Chan%20Chee%20Pin.pdf |