Earth-air Heat Exchangers For Passive Air Conditioning: Case Study Burkina Faso
An earth-air heat exchanger (EAHX), also known as an earth tube heat exchanger or Canadian well, is a system for cooling and heating buildings using the ground as a heat sink/source. This study examines the ground temperature gradient and the performance of an EAHX performance in Burkina Faso. G...
| Main Authors: | , , |
|---|---|
| Format: | Article |
| Language: | English |
| Published: |
Penerbit Universiti Sains Malaysia
2012
|
| Subjects: | |
| Online Access: | http://eprints.usm.my/42121/ http://eprints.usm.my/42121/1/Art_2_jcdc17-1.pdf |
| _version_ | 1848879474451415040 |
|---|---|
| author | Woodson, Thomas Coulibaly, Yézouma Traoré, Eric Seydou |
| author_facet | Woodson, Thomas Coulibaly, Yézouma Traoré, Eric Seydou |
| author_sort | Woodson, Thomas |
| building | USM Institutional Repository |
| collection | Online Access |
| description | An earth-air heat exchanger (EAHX), also known as an earth tube heat exchanger
or Canadian well, is a system for cooling and heating buildings using the ground as a heat
sink/source. This study examines the ground temperature gradient and the performance of
an EAHX performance in Burkina Faso. Ground temperature measurements were made at
depths of 0.5 m, 1.0 m and 1.5 m. At the hottest time of the day, 15:00, the average outside
temperature was 39.0°C, but the average temperature 1.5 m underground was 30.4°C. A
clear phase shift was observed between the maximum outside temperature and the
maximum ground temperature: the time of the day when the outside temperature is highest
corresponds to the time when the underground temperature was lowest. The EAHX was 25 m
long, 1.5 m underground and used a 95 m3/hr ventilator. It was able to cool the air drawn in
from the outside by 7.6°C. |
| first_indexed | 2025-11-15T17:47:48Z |
| format | Article |
| id | usm-42121 |
| institution | Universiti Sains Malaysia |
| institution_category | Local University |
| language | English |
| last_indexed | 2025-11-15T17:47:48Z |
| publishDate | 2012 |
| publisher | Penerbit Universiti Sains Malaysia |
| recordtype | eprints |
| repository_type | Digital Repository |
| spelling | usm-421212018-09-26T09:10:00Z http://eprints.usm.my/42121/ Earth-air Heat Exchangers For Passive Air Conditioning: Case Study Burkina Faso Woodson, Thomas Coulibaly, Yézouma Traoré, Eric Seydou TH1-9745 Building construction An earth-air heat exchanger (EAHX), also known as an earth tube heat exchanger or Canadian well, is a system for cooling and heating buildings using the ground as a heat sink/source. This study examines the ground temperature gradient and the performance of an EAHX performance in Burkina Faso. Ground temperature measurements were made at depths of 0.5 m, 1.0 m and 1.5 m. At the hottest time of the day, 15:00, the average outside temperature was 39.0°C, but the average temperature 1.5 m underground was 30.4°C. A clear phase shift was observed between the maximum outside temperature and the maximum ground temperature: the time of the day when the outside temperature is highest corresponds to the time when the underground temperature was lowest. The EAHX was 25 m long, 1.5 m underground and used a 95 m3/hr ventilator. It was able to cool the air drawn in from the outside by 7.6°C. Penerbit Universiti Sains Malaysia 2012 Article PeerReviewed application/pdf en http://eprints.usm.my/42121/1/Art_2_jcdc17-1.pdf Woodson, Thomas and Coulibaly, Yézouma and Traoré, Eric Seydou (2012) Earth-air Heat Exchangers For Passive Air Conditioning: Case Study Burkina Faso. Journal of Construction in Developing Countries , 17 (1). pp. 21-32. ISSN 1823-6499 http://web.usm.my/jcdc/vol17_1_2012/Art%202_jcdc17-1.pdf |
| spellingShingle | TH1-9745 Building construction Woodson, Thomas Coulibaly, Yézouma Traoré, Eric Seydou Earth-air Heat Exchangers For Passive Air Conditioning: Case Study Burkina Faso |
| title | Earth-air Heat Exchangers For Passive Air Conditioning: Case Study
Burkina Faso |
| title_full | Earth-air Heat Exchangers For Passive Air Conditioning: Case Study
Burkina Faso |
| title_fullStr | Earth-air Heat Exchangers For Passive Air Conditioning: Case Study
Burkina Faso |
| title_full_unstemmed | Earth-air Heat Exchangers For Passive Air Conditioning: Case Study
Burkina Faso |
| title_short | Earth-air Heat Exchangers For Passive Air Conditioning: Case Study