An inverse time admittance relay for fault detection in distribution networks containing DGs

Isolation of a faulted segment, from either side of a fault, in a radial feeder that has several converter interfaced DGs is a challenging task when current sensing protective devices are employed. The protective device, even if it senses a downstream fault, may not operate if fault current level is...

Full description

Bibliographic Details
Main Authors: Dewadasa, M., Ghosh, Arindam, Ledwich, G.
Other Authors: -
Format: Conference Paper
Published: Institute of Electrical and Electronics Engineers ( IEEE ) 2009
Online Access:http://hdl.handle.net/20.500.11937/43579
Description
Summary:Isolation of a faulted segment, from either side of a fault, in a radial feeder that has several converter interfaced DGs is a challenging task when current sensing protective devices are employed. The protective device, even if it senses a downstream fault, may not operate if fault current level is low due to the current limiting operation of converters. In this paper, a new inverse type relay is introduced based on line admittance measurement to protect a distribution network, which has several converter interfaced DGs. The basic operation of this relay, its grading and reach settings are explained. Moreover a method is proposed to compensate the fault resistance such that the relay operation under this condition is reliable. Then designed relay performances are evaluated in a radial distribution network. The results are validated through PSCAD/EMTDC simulation and MATLAB calculations