Impact of high PV penetration on distribution transformer insulation life

The reliable operation of distribution systems is critically dependent on detailed understanding of load impacts on distribution transformer insulation systems. This paper estimates the impact of rooftop photovoltaic (PV) generation on a typical 200-kVA, 22/0.415-kV distribution transformer life und...

Full description

Bibliographic Details
Main Authors: Pezeshki, H., Wolfs, Peter, Ledwich, G.
Format: Journal Article
Published: Institute of Electrical and Electronics Engineers Inc. 2014
Online Access:http://hdl.handle.net/20.500.11937/30357
Description
Summary:The reliable operation of distribution systems is critically dependent on detailed understanding of load impacts on distribution transformer insulation systems. This paper estimates the impact of rooftop photovoltaic (PV) generation on a typical 200-kVA, 22/0.415-kV distribution transformer life under different operating conditions. This transformer supplies a suburban area with a high penetration of roof top photovoltaic systems. The transformer loads and the phase distribution of the PV systems are significantly unbalanced. Oil and hot-spot temperature and remnant life of distribution transformer under different PV and balance scenarios are calculated. It is shown that PV can significantly extend the transformer life.